Connecting the power cables
DANGER
- Only qualified electricians are allowed to work on the electrical system.
- RISK OF SHORT-CIRCUIT! Connect the power cables to the correct ports inside the Solar Life that agree with the building’s electrical installation.
To access the internal cable connections, remove the trim cover Ⓐ and the sealing cover Ⓞ. See Removing and installing the covers.
Connecting to a 1-phase grid with Neutral
The 1-phase connection applies to the following IEC earth grounding connection types: TT, TN-S and TN-C-S.
To connect Solar Life to a 1-phase grid with Neutral:
- Connect the phase wire L1 (brown) to L1.
- Connect the neutral wire N (blue) to N.
- Connect the protective earth wire PE (yellow/green) to PE.
- If applicable, tighten the power cable gland Ⓔ.
Connecting to a 3-phase grid with Neutral
The 3-phase connection applies to the following IEC earth grounding connection types: TT, TN-S and TN-C-S.
To connect Solar Life to a 3-phase grid with Neutral:
- Connect the phase wire L1 (brown) to L1.
- Connect the phase wire L2 (black) to L2.
- Connect the phase wire L3 (grey) to L3.
- Connect the neutral wire N (blue) to N.
- Connect the protective earth wire PE (yellow/green) to PE.
- If applicable, tighten the power cable gland Ⓔ.
Connecting to a 1-phase grid without Neutral
|
|
WARNING! Make sure that the phase that has VLX-VPE ≈ 0 is used as a neutral line. Using L3 in the schematics is for illustrative purposes only. |
The 1-phase connection without Neutral applies to the following IEC earth grounding connection types: IT and grid without Neutral.
To connect Solar Life to a 1-phase grid without Neutral:
- Connect the phase wire L1 (brown) to L1.
- Connect the phase wire L3 (grey) to N.
- Connect the protective earth wire PE (yellow/green) to PE.
- If applicable, tighten the power cable gland Ⓔ.
|
|
Assumptions: Phase L3 is available next to L1 VL3 - VPE ≈ 0 |
Connecting to a 3-phase grid without Neutral
|
|
WARNING! Make sure that the phase that has VLX-VPE ≈ 0 is used as a neutral line. Using L3 in the schematics is for illustrative purposes only. |
The 3-phase connection without Neutral applies to the following IEC earth grounding connection types: IT and grid without Neutral.
To connect Solar Life to a 3-phase grid without Neutral:
- Connect the phase wire L1 (brown) to L1.
- Connect the phase wire L2 (black) to L2.
- Connect the phase wire L3 (grey) to N.
- Connect the protective earth wire PE (yellow/green) to PE.
- If applicable, tighten the power cable gland Ⓔ.
|
|
Assumptions: Phase L3 is available next to L1 VL3 - VPE ≈ 0 |